Check required CO₂ cylinder bank capacity against protected-space volume - 35 % design concentration for cargo holds, 40 % engine-room.
Formula
$$ m = V \cdot c \cdot 1.977, \ n = \lceil m/m_{cyl}\rceil $$
Symbol legend
| Symbol | Meaning | Unit | Source |
|---|---|---|---|
| $V$ | Protected space volume | m³ | capacity plan |
| $c$ | Design concentration | - | FSS Ch.5 |
Sources
- FSS Code Ch. 5.