Real-power split between two generators in droop mode when the grid frequency shifts.
Formula
$$ P_i = P_\text{total} \cdot \frac{k_i}{\sum k}, \quad k_i = \frac{\text{MW}_i}{\text{droop}_i} $$Symbol legend
| Symbol | Meaning | Unit | Source |
|---|---|---|---|
| $\text{MW}_i$ | Rated real power of gen i | MW | nameplate |
| $\text{droop}_i$ | Governor droop setting | - | governor |
| $P_i$ | Real-power share | MW | result |
Sources
- IACS UR E22 - Power management systems.