ShipCalculators.com

IDMT Relay Operating Time (IEC 60255)

Contents

Live calculator

Time to trip for an inverse-time overcurrent relay following IEC 60255 normal/very/extremely inverse curves.

Formula

$$ t_{op} = \frac{k \cdot \text{TMS}}{(I/I_p)^a - 1} $$

Symbol legend

SymbolMeaningUnitSource
$I$Actual fault currentACT secondary × ratio
$I_p$Pickup currentArelay setting
$k, a$Curve constants-IEC 60255
$TMS$Time multiplier setting-relay setting
$t_{op}$Operating timesresult

Sources

  • IEC 60255-151 - Measuring relays and protection equipment.