Earth-fault leakage current for marine IT (isolated) distribution - the basis for alarm-setting on insulation-monitoring devices.
Formula
$$ I_L = \frac{U_n}{\sqrt 3 X_C}, \quad X_C = \frac{1}{2\pi f C} $$
Symbol legend
| Symbol | Meaning | Unit | Source |
|---|---|---|---|
| $U_n$ | Nominal voltage | V | switchboard rating |
| $C$ | Network capacitance | µF | cable + equipment |
Sources
- IEC 60092-507.