HomeCalculatorsRefrigerant Charge (Tube Volume Method)

Refrigerant Charge (Tube Volume Method)

Estimate refrigerant charge from system pipe + component internal volume and refrigerant density at operating states.

Refrigeration
Liquid-line volume
4.02L
Suction-line volume
15.39L
Estimated charge
25.38kg
Formula, assumptions, and limits

Approximate - assumes the liquid line + condenser + receiver are liquid-filled at condensing density, suction line is vapour-filled at evaporating density. Accurate to ±10 % for most DX plants. For flooded systems add evaporator liquid charge.

Symbol legend

SymbolMeaningUnitSource
Pipe internal volume (πD²L/4)geometry
Liquid refrigerant densitykg/m³P-h chart
Suction vapour densitykg/m³P-h chart