CO₂ Cylinder Bank (Machinery Space)
CO₂ mass for an engine-room fixed extinguishing system at 40 % volume concentration per FSS Code Ch.5.
CO₂ volume at 1 atm
2,000.0m³
CO₂ mass
3,960kg
Cylinders @ 45 kg each
88 -
Formula, assumptions, and limits
CO₂ vapour density at 15 °C atm = 1.98 kg/m³. Total-flooding design must deliver 85 % of the rated charge within 2 min for machinery spaces (FSS Ch.5 §2.2.1). Rooms must be sealed to maintain concentration for at least 10 min.
Symbol legend
| Symbol | Meaning | Unit | Source |
|---|---|---|---|
| Gross volume of protected space | m³ | GA plan | |
| Design concentration (vol fraction) | % | FSS Code table | |
| CO₂ density at 1 atm 15 °C | kg/m³ | 1.98 |