HomeCalculatorsCO₂ Cylinder Bank (Machinery Space)

CO₂ Cylinder Bank (Machinery Space)

CO₂ mass for an engine-room fixed extinguishing system at 40 % volume concentration per FSS Code Ch.5.

Fire safetyCO₂
CO₂ volume at 1 atm
2,000.0
CO₂ mass
3,960kg
Cylinders @ 45 kg each
88 -
Formula, assumptions, and limits

CO₂ vapour density at 15 °C atm = 1.98 kg/m³. Total-flooding design must deliver 85 % of the rated charge within 2 min for machinery spaces (FSS Ch.5 §2.2.1). Rooms must be sealed to maintain concentration for at least 10 min.

Symbol legend

SymbolMeaningUnitSource
Gross volume of protected spaceGA plan
Design concentration (vol fraction)%FSS Code table
CO₂ density at 1 atm 15 °Ckg/m³1.98